InstallationandOperationManual(REVH) PVI6500/PVI7500

23
TwoRJ45connectorsareusedforexternalcommunicationtoaSolectriacommunicationgateway.TheACterminalblockis
usedtoconnecttothebuilding/utilitygridthroughadedicatedcircuitbreakerinthebuildingdistributionpanel.
WARNING!
Allelectricalworkshallbedoneinaccordancewiththelocalandnational
electricalcodesandshouldfollow
theimportantsafetyinstructionsinthismanual.
 WARNING!
Localandnationalelectricalcodesstatethattheinvertermustbeconnectedtoadedicatedcircuit,andthat
nootheroutletsordevicescanbeconnectedtothesamecircuit.Thecodealsoimposeslimitationsonthe
sizeoftheinverterandthemannerinwhichitisconnected
totheutilitygird.
 WARNING!
Make sure that you use suitable conductors for both the AC and DC wiring. The conductors must be
adequatelysizedandofcorrecttemperatureratingandsunlightresistantifneeded.Useonly#10AWGto
#6 AWG, 90C (194F) stranded or solid copper wire (but not fine
stranded wire) for all AC and DC wiring
connectionstothePVI6500/7500inverter.
 WARNING!
PV arrays will be energized when exposed to light.Cover the arrays with opaque materials during
installationandwiring,and/orkeepmoduleleadsdisconnected.
BeforewiringthePVI65007500inverter, theinstaller needstodeterminethegridconnection/utilityconfigurationthat the
inverterwillbeconnectedto.The
inverterisdefaultsetforutilityinterconnectionwithaneutralconnection.However,itmay
bereconfiguredforaconnectionwithoutaneutral.Theutilityvoltageconfigurationjumpers,J210,arelocatedonthecontrol
boardasshowninfigure2.3.7areusedtosettheinvertertobeconnectedtothecommonly
usedutilityconfigurationtypes
shown in the figure 2.3.8.As shown in the figure 2.3.7, the P1 and P2 pins are used to configure the inverter for the
connectiontypesof208V,240Vand277VACoutputswithorwithoutneutral(withneutralonlyfor277V).Whentheinverteris
set
for the connection configurations with neutral, it can automatically detect the utility voltage and adjust the output AC
voltageaccordingthegridvoltage.
Fig2.3.7Building/Utilityvoltageconfigurationjumpers(qualifiedpersonnelonly)
P1
P2
P3
P3
P2
P1
277V / 240V / 208V
With Neutral (Default)
240
V Without Neutral
208V Without Neutral
P1
P3
FAN Auto (Default)
FAN On
P2
J210